0 Review(s)

| Model | S5-GC50K | S5-GC60K |
|---|---|---|
| DC Input | ||
| Max. Input Voltage | 1100 V | |
| Nominal Voltage | 600 V | |
| Starting Voltage | 195 V | |
| MPPT Voltage Range | 180–1000 V | |
| Max. Input Current | 5 × 32 A | 6 × 32 A |
| Max. Short Circuit Current | 5 × 40 A | 6 × 40 A |
| No. of MPPTs / Max. Input Strings per MPPT | 5 / 10 | 6 / 12 |
| AC Output | ||
| Nominal Output Power | 50 kW | 60 kW |
| Nominal Apparent Power | 55 kVA | 66 kVA |
| Max. Output Power | 55 kW | 66 kW |
| Nominal Grid Voltage | 3/N/PE, 220 V / 380 V, 230 V / 400 V | |
| Nominal Grid Frequency | 50 Hz / 60 Hz | |
| Nominal Output Current | 76.0 A / 72.2 A | 91.2 A / 86.6 A |
| Max. Output Current | 83.6 A | 100.3 A |
| Power Factor | >0.99 (adjustable from 0.8 leading to 0.8 lagging) | |
| THDi | <3% | |
| Efficiency | ||
| Max. Efficiency | 98.7% | |
| European Efficiency | 98.3% | |
| Protection | ||
| DC Reverse Polarity Protection | Yes | |
| Short Circuit Protection | Yes | |
| Output Overcurrent Protection | Yes | |
| Surge Protection | DC Type II / AC Type II | |
| Grid Monitoring | Yes | |
| Anti-islanding Protection | Yes | |
| Temperature Protection | Yes | |
| String Monitoring | Yes | |
| I/V Curve Scanning | Yes | |
| Multiple Peak Tracking | Yes | |
| Built-in AFCI 2.0 | Optional | |
| Built-in PID Recovery | Optional | |
| Integrated DC Switch | Yes | |
| General Data | ||
| Dimensions (W × H × D) | 691 × 578 × 338 mm | |
| Weight | 53.7 kg | |
| Topology | Transformerless | |
| Self-consumption | <1 W | |
| Operating Temperature Range | –25 °C ~ +60 °C | |
| Relative Humidity | 0 – 100% | |
| Ingress Protection Rating | IP66 | |
| Noise Emission (typical) | <55 dB(A) | |
| Cooling Concept | Smart Fan Cooling | |
| Max. Operating Altitude | 4000 m | |
| Grid Connection Standard | G99, VDE-AR-N 4105/VDE 0124, EN 50549-1, VDE 0126/UTE C15/FR:2019, RD 1699/RD 244/UNE 206006/UNE 206007-1, CEI 0-21, C10/11, NRS 097-2-1, EIFS 2018.2, IEC 62116, CEI 61727, IEC 60068, IEC 61683, EN 50530 | |
| Safety / EMC Standard | IEC 62109-1/2, IEC 62116 & IEC 61000-6-1/-2/-3/-4 | |
| Features | ||
| DC Connection | MC4 Connector | |
| AC Connection | OT Terminal (max. 70 mm²) | |
| Display | LCD | |
| Communication | RS485, USB, Optional: Wi-Fi, GPRS | |